Rinnai 05

Rinnai code 05: bypass flow control fault

Short answer

Code 05 is a fault with the bypass flow control device, a valve that mixes some cold water into the hot to help hold a steady outlet temperature. On older models Rinnai says to cycle the power and run hot water; if code 05 returns, the bypass valve is replaced. On SENSEI models a technician tests it first.

In this guide
  1. What to try first
  2. What a technician does
  3. A note on hybrid models
  4. Before you call

Inside many Rinnai heaters, a small motorized bypass valve blends some cold water with the heated water. Code 05 means the control board is not getting the response it expects from that valve.

The meaning and service steps below come from Rinnai's own diagnostic code guide for its tankless water heaters.

What to try first

  1. Turn off the power to the heater, then turn it back on.
  2. Open a hot tap and let the heater fire.
  3. If code 05 appears again, the valve likely needs replacing.

What a technician does

On SENSEI models, Rinnai tells technicians to measure the valve's resistance at the control board before replacing it. On older models, the fix after a failed power cycle is a new bypass valve.

A note on hybrid models

Rinnai lists different checks for code 05 on its RH180 hybrid tank-tankless units: cleaning the air filter and inspecting the venting for obstructions and correct clearances. If you have one of those, start there.

Before you call

Have the model and serial number from the rating label ready, along with the exact code and when it appears: at startup, during use, or only at high demand. Mention any recent work on the gas, water or electrical supply and when the heater was last descaled. This helps the technician bring the right parts and often saves a second visit.

See every code on our Rinnai error codes page.

Common questions

Can I keep using hot water with Rinnai code 05?

Sometimes the heater still runs but temperature control may be poor. Have it checked so a small valve problem does not become a bigger one.

Was this article helpful?

Other Rinnai codes

CodeMeaning
02 No burner operation during freeze protection
03 Power interruption during bath fill
05 Bypass flow control device fault
10 Air supply, exhaust blockage or condensate trap full
11 No ignition
12 Flame failure
14 Thermal fuse or overheat sensor tripped
15 Venturi control fault
16 Outgoing water temperature too high (safety shutdown)
17 Venturi blockage
19 Electrical grounding fault
21 Data transfer error after a control board replacement
25 Condensate drain clogged or condensate pump error
32 Outgoing water temperature sensor (thermistor) fault
33 Heat exchanger temperature sensor (thermistor) fault
34 Combustion air temperature sensor fault
38 Exhaust gas temperature sensor fault
41 Freeze protection sensor fault
51 Inlet water temperature sensor fault
52 Gas valve or modulating solenoid valve signal fault
54 High exhaust gas temperature
57 Burner overheat switch open
58 Secondary heat exchanger overheat
61 Combustion fan motor fault
63 Recirculation low flow
65 Water flow control device (servo) fault
70 Control board (PC board) fault
71 Gas solenoid valve circuit fault
72 Flame rod (flame sensing) fault
73 Burner thermocouple fault
79 Water leak detected inside the unit
LC Scale buildup in the heat exchanger
SS Service soon (maintenance reminder)
FF Maintenance has been performed (service history marker)