Rinnai 51

Rinnai code 51: inlet water temperature sensor fault

Short answer

Code 51 is a fault with the inlet water temperature thermistor, the sensor that measures how cold the incoming water is. Rinnai's steps are to check the wiring, drain the unit, remove the sensor and clean off any scale, test its resistance, and replace it if it fails.

In this guide
  1. Common causes
  2. What a technician does
  3. How to reset it
  4. Before you call

To reach your set temperature quickly, a tankless heater needs to know how cold the incoming water is. The inlet water thermistor provides that reading. Code 51 means the reading is not valid.

The meaning and service steps below come from Rinnai's own diagnostic code guide for its tankless water heaters.

Common causes

  • Scale on the sensor, especially with hard water
  • Loose, broken or damaged wiring back to the control board
  • A failed sensor

What a technician does

  1. Checks the wiring harness.
  2. Shuts off the water supply and drains the unit.
  3. Removes the sensor, cleans off any buildup and tests its resistance, which should drop as it warms.
  4. Reinstalls it or replaces it, then checks for leaks.

How to reset it

  1. Close all hot water taps.
  2. Turn the water heater off at the temperature controller, wait about a minute, then turn it back on.
  3. Open a hot tap and watch whether the code returns.

If the same code keeps coming back, the cause is still there. Repeated resets are not a repair.

Codes 32, 33 and 51 are all temperature sensor faults. If you have seen more than one of them, scale is a likely common cause.

Before you call

Have the model and serial number from the rating label ready, along with the exact code and when it appears: at startup, during use, or only at high demand. Mention any recent work on the gas, water or electrical supply and when the heater was last descaled. This helps the technician bring the right parts and often saves a second visit.

See every code on our Rinnai error codes page.

Common questions

Can hard water cause Rinnai code 51?

Yes. Scale on the sensor can throw off its reading. Regular descaling helps prevent it.

Was this article helpful?

Other Rinnai codes

CodeMeaning
02 No burner operation during freeze protection
03 Power interruption during bath fill
05 Bypass flow control device fault
10 Air supply, exhaust blockage or condensate trap full
11 No ignition
12 Flame failure
14 Thermal fuse or overheat sensor tripped
15 Venturi control fault
16 Outgoing water temperature too high (safety shutdown)
17 Venturi blockage
19 Electrical grounding fault
21 Data transfer error after a control board replacement
25 Condensate drain clogged or condensate pump error
32 Outgoing water temperature sensor (thermistor) fault
33 Heat exchanger temperature sensor (thermistor) fault
34 Combustion air temperature sensor fault
38 Exhaust gas temperature sensor fault
41 Freeze protection sensor fault
51 Inlet water temperature sensor fault
52 Gas valve or modulating solenoid valve signal fault
54 High exhaust gas temperature
57 Burner overheat switch open
58 Secondary heat exchanger overheat
61 Combustion fan motor fault
63 Recirculation low flow
65 Water flow control device (servo) fault
70 Control board (PC board) fault
71 Gas solenoid valve circuit fault
72 Flame rod (flame sensing) fault
73 Burner thermocouple fault
79 Water leak detected inside the unit
LC Scale buildup in the heat exchanger
SS Service soon (maintenance reminder)
FF Maintenance has been performed (service history marker)

All Rinnai error codes