Rinnai 70

Rinnai code 70: control board fault

Short answer

Code 70 is a PC board fault. Rinnai's steps are to check that all heater settings were set properly, check every wiring harness at the board for loose or damaged connections, and then replace the board. On SENSEI models the settings are transferred from the old board to the new one with a data cable or programmed by hand.

In this guide
  1. Checks before a new board
  2. After a board replacement
  3. How to reset it
  4. Protecting the board
  5. Before you call

The PC board is the heater's control center. Code 70 means it has detected a fault in its own operation or setup.

The meaning and service steps below come from Rinnai's own diagnostic code guide for its tankless water heaters.

Checks before a new board

  1. Confirm the heater's settings (parameters) were set correctly during installation.
  2. Check every wiring harness at the board for loose, broken or damaged connections.
  3. Only then replace the board.

After a board replacement

On SENSEI and SENSEI RX/CX models, Rinnai has technicians move the settings from the old board to the new one using a data transfer cable included with the new board. If that is not possible, the settings are programmed by hand following Rinnai's instructions. Skipping this step can cause new problems.

How to reset it

  1. Close all hot water taps.
  2. Turn the water heater off at the temperature controller, wait about a minute, then turn it back on.
  3. Open a hot tap and watch whether the code returns.

If the same code keeps coming back, the cause is still there. Repeated resets are not a repair.

Protecting the board

  • Use a properly grounded outlet and consider an appliance-rated surge protector.
  • Keep water from dripping onto the unit from pipes or the vent.

A control board is one of the pricier parts on a tankless heater, so check whether it is still under warranty before paying for one.

Before you call

Have the model and serial number from the rating label ready, along with the exact code and when it appears: at startup, during use, or only at high demand. Mention any recent work on the gas, water or electrical supply and when the heater was last descaled. This helps the technician bring the right parts and often saves a second visit.

See every code on our Rinnai error codes page.

Common questions

Can a power surge cause Rinnai code 70?

Surges can damage control boards. If the code started after a storm or outage, mention it to your technician.

Was this article helpful?

Other Rinnai codes

CodeMeaning
02 No burner operation during freeze protection
03 Power interruption during bath fill
05 Bypass flow control device fault
10 Air supply, exhaust blockage or condensate trap full
11 No ignition
12 Flame failure
14 Thermal fuse or overheat sensor tripped
15 Venturi control fault
16 Outgoing water temperature too high (safety shutdown)
17 Venturi blockage
19 Electrical grounding fault
21 Data transfer error after a control board replacement
25 Condensate drain clogged or condensate pump error
32 Outgoing water temperature sensor (thermistor) fault
33 Heat exchanger temperature sensor (thermistor) fault
34 Combustion air temperature sensor fault
38 Exhaust gas temperature sensor fault
41 Freeze protection sensor fault
51 Inlet water temperature sensor fault
52 Gas valve or modulating solenoid valve signal fault
54 High exhaust gas temperature
57 Burner overheat switch open
58 Secondary heat exchanger overheat
61 Combustion fan motor fault
63 Recirculation low flow
65 Water flow control device (servo) fault
70 Control board (PC board) fault
71 Gas solenoid valve circuit fault
72 Flame rod (flame sensing) fault
73 Burner thermocouple fault
79 Water leak detected inside the unit
LC Scale buildup in the heat exchanger
SS Service soon (maintenance reminder)
FF Maintenance has been performed (service history marker)

All Rinnai error codes