Rinnai code 54: high exhaust temperature

Short answer

Code 54 means the exhaust got too hot. Rinnai explains that above 163°F the heater first lowers its firing rate, and if the exhaust stays that hot for 120 seconds it shuts down with code 54. Checks include vent clearances and restrictions, vent length, gas type, inlet water temperature and scale in the heat exchanger.

In this guide
  1. How the shutdown works
  2. What Rinnai lists as causes
  3. The scale connection
  4. How to reset it
  5. Before you call

Exhaust from a tankless heater should stay within a safe temperature range. When it gets too hot, the heater protects itself and its vent pipe by shutting down.

The meaning and service steps below come from Rinnai's own diagnostic code guide for its tankless water heaters.

How the shutdown works

According to Rinnai, when exhaust temperature passes 163°F the heater reduces its gas input. If the exhaust is still above 163°F after 120 seconds, it shuts off and shows code 54.

What Rinnai lists as causes

  • Vent termination clearances not met, or restrictions in the intake or exhaust
  • Venting longer or different from Rinnai's specifications
  • A heater running on a different gas type than its rating plate shows
  • Incoming water hotter than 160°F
  • Scale inside the heat exchanger, which shows up as hot spots on its surface

The scale connection

When scale lines the heat exchanger, heat cannot move into the water, so more of it leaves with the exhaust. Rinnai's fix is to flush the heat exchanger with vinegar following the owner's manual. If you have hard water and the unit has not been flushed in a year or more, this is the likely cause.

How to reset it

  1. Close all hot water taps.
  2. Turn the water heater off at the temperature controller, wait about a minute, then turn it back on.
  3. Open a hot tap and watch whether the code returns.

If the same code keeps coming back, the cause is still there. Repeated resets are not a repair.

Before you call

Have the model and serial number from the rating label ready, along with the exact code and when it appears: at startup, during use, or only at high demand. Mention any recent work on the gas, water or electrical supply and when the heater was last descaled. This helps the technician bring the right parts and often saves a second visit.

See every code on our Rinnai error codes page.

Common questions

Can I fix Rinnai code 54 by descaling?

If scale is the cause, yes. Check the vent first, then flush the heat exchanger as your manual describes.

Was this article helpful?

Other Rinnai codes

CodeMeaning
02 No burner operation during freeze protection
03 Power interruption during bath fill
05 Bypass flow control device fault
10 Air supply, exhaust blockage or condensate trap full
11 No ignition
12 Flame failure
14 Thermal fuse or overheat sensor tripped
15 Venturi control fault
16 Outgoing water temperature too high (safety shutdown)
17 Venturi blockage
19 Electrical grounding fault
21 Data transfer error after a control board replacement
25 Condensate drain clogged or condensate pump error
32 Outgoing water temperature sensor (thermistor) fault
33 Heat exchanger temperature sensor (thermistor) fault
34 Combustion air temperature sensor fault
38 Exhaust gas temperature sensor fault
41 Freeze protection sensor fault
51 Inlet water temperature sensor fault
52 Gas valve or modulating solenoid valve signal fault
54 High exhaust gas temperature
57 Burner overheat switch open
58 Secondary heat exchanger overheat
61 Combustion fan motor fault
63 Recirculation low flow
65 Water flow control device (servo) fault
70 Control board (PC board) fault
71 Gas solenoid valve circuit fault
72 Flame rod (flame sensing) fault
73 Burner thermocouple fault
79 Water leak detected inside the unit
LC Scale buildup in the heat exchanger
SS Service soon (maintenance reminder)
FF Maintenance has been performed (service history marker)