Rinnai 34

Rinnai code 34: combustion air sensor fault

Short answer

Code 34 is a temperature sensor fault. On older non-SENSEI Rinnai models it is the combustion air temperature sensor in the fan housing; on SENSEI RX/CX models Rinnai lists it as the lime detecting sensor. Technicians check the wiring, then test the sensor's resistance and replace it if it fails.

In this guide
  1. Which sensor it is
  2. What a technician does
  3. How to reset it
  4. If you have an RX/CX model
  5. Before you call

Code 34 means one of the heater's temperature sensors, called thermistors, is giving an invalid reading. Which sensor depends on your model.

The meaning and service steps below come from Rinnai's own diagnostic code guide for its tankless water heaters.

Which sensor it is

Model seriesSensor behind code 34
Non-SENSEICombustion air temperature sensor in the fan housing
SENSEI RX/CXLime detecting sensor, which helps the heater watch for scale

What a technician does

  1. Checks the wiring from the sensor back to the control board.
  2. Removes the sensor and tests its resistance, which should drop as it warms.
  3. Replaces the sensor if it does not respond correctly.

How to reset it

  1. Close all hot water taps.
  2. Turn the water heater off at the temperature controller, wait about a minute, then turn it back on.
  3. Open a hot tap and watch whether the code returns.

If the same code keeps coming back, the cause is still there. Repeated resets are not a repair.

If you have an RX/CX model

Because the sensor on these models relates to scale detection, ask the technician whether the heat exchanger is due for a flush. In hard water areas, plan to descale a tankless water heater about once a year.

Before you call

Have the model and serial number from the rating label ready, along with the exact code and when it appears: at startup, during use, or only at high demand. Mention any recent work on the gas, water or electrical supply and when the heater was last descaled. This helps the technician bring the right parts and often saves a second visit.

See every code on our Rinnai error codes page.

Common questions

Is Rinnai code 34 expensive to fix?

The sensor itself is a small part. Most of the cost is the service call and labor.

Was this article helpful?

Other Rinnai codes

CodeMeaning
02 No burner operation during freeze protection
03 Power interruption during bath fill
05 Bypass flow control device fault
10 Air supply, exhaust blockage or condensate trap full
11 No ignition
12 Flame failure
14 Thermal fuse or overheat sensor tripped
15 Venturi control fault
16 Outgoing water temperature too high (safety shutdown)
17 Venturi blockage
19 Electrical grounding fault
21 Data transfer error after a control board replacement
25 Condensate drain clogged or condensate pump error
32 Outgoing water temperature sensor (thermistor) fault
33 Heat exchanger temperature sensor (thermistor) fault
34 Combustion air temperature sensor fault
38 Exhaust gas temperature sensor fault
41 Freeze protection sensor fault
51 Inlet water temperature sensor fault
52 Gas valve or modulating solenoid valve signal fault
54 High exhaust gas temperature
57 Burner overheat switch open
58 Secondary heat exchanger overheat
61 Combustion fan motor fault
63 Recirculation low flow
65 Water flow control device (servo) fault
70 Control board (PC board) fault
71 Gas solenoid valve circuit fault
72 Flame rod (flame sensing) fault
73 Burner thermocouple fault
79 Water leak detected inside the unit
LC Scale buildup in the heat exchanger
SS Service soon (maintenance reminder)
FF Maintenance has been performed (service history marker)

All Rinnai error codes